Type A vs Type B RCD (6 mA DC Leakage Detection)

The residual current protection of an EV charger must also cover DC leakage, using either a Type B RCD or a Type A RCD plus 6 mA DC detection.

Technical level:Advanced

In the event of a fault, an electric vehicle can produce smooth DC leakage current. Ordinary Type AC RCDs cannot detect it, and a Type A RCD can be "blinded" by it and fail to trip during a dangerous leak.

That is why the installation standard for charging points requires either a 30 mA Type B RCD or a 30 mA Type A RCD together with a 6 mA DC leakage detection device. Many wallboxes have this detection built in, in which case a Type A RCD in the panel is enough.

A common mistake is fitting a Type AC RCD on the charger circuit, or assuming the built-in detection is there. Check the datasheet and, if it does not explicitly mention 6 mA DC detection, install a Type B.