- Published:
- Updated:
UPS runtime: how long it lasts and how to calculate it
Calculate UPS runtime with a formula, worked home and 8 kW examples, a device power table and practical ways to extend backup time.
Short answer: how long a UPS lasts depends on its load and batteries. Datasheets usually specify a few minutes at full load, but with a lighter load—for example, just a router and NAS device—the same UPS can run several times longer. Below you will find manufacturer specifications, a quick calculation for home use and the detailed formula for larger loads.
What determines runtime?
One of the most important factors in choosing the right UPS is how much runtime it needs to provide during a power outage. The type and number of batteries in the UPS determine its runtime.
The relationship between load and runtime is not linear: halving the load usually more than doubles runtime, because lead-acid batteries deliver more energy when discharged slowly. Battery age and temperature also matter.
What the specifications show
| Model | Power | Runtime at 50% load | Runtime at 100% load |
|---|---|---|---|
| LEO LCD 650AP (Line Interactive) | 650 VA / 390 W | 10 minutes | 4 minutes |
| LEO LCD 1500AP (Line Interactive) | 1,500 VA / 900 W | 7 minutes | 4 minutes |
| PRIME PLUS 1101 SRT (Online) | 1,000 VA / 1,000 W | 11 minutes | 3 minutes |
| LiON 1102 SRT B (Online, lithium) | 2,000 VA / 1,800 W | 26 minutes | 15 minutes |
For the same UPS, runtime at a 10–20% load is several times longer than the figures in the table.
A quick calculation for home and office
Runtime (hours) ≈ (battery voltage × Ah × number of batteries × 0.7) ÷ load in W
The 0.7 factor accounts for UPS losses and the battery's usable capacity. Example: a UPS with one 12 V 9 Ah battery and a 60 W load (router, NAS device and a small switch): (12 × 9 × 1 × 0.7) ÷ 60 ≈ 1.3 hours. At very light loads, the UPS itself consumes some of the energy, so the actual runtime is slightly shorter.
Typical power consumption for the calculation:
| Device | Typical power consumption |
|---|---|
| Wi-Fi router | 10–20 W |
| Two-drive NAS device | 25–40 W |
| Cameras (2–4) and recorder | 40–60 W |
| Office computer and monitor | 80–150 W |
| LED TV | 60–150 W |
| Gaming PC during gameplay | 300–500 W |
The most reliable method: with your devices connected, unplug the UPS from the wall outlet and measure the runtime.
The detailed formula for large loads
The calculation can be made using the following formula:
C = (P × T) ÷ (V × η × K)
where:
- C – Battery capacity, in amp-hours (Ah)
- P – Load power, in watts (W)
- T – Runtime, in hours (h)
- V – Nominal battery voltage, in volts (V)
- η – Battery inverter efficiency
- K – Battery discharge factor
- When battery runtime is <3h, K = 0.6
- When battery runtime is 3~5h, K = 0.8
- When battery runtime is 5~10h, K = 0.85
- When battery runtime is >10h, K = 1
For example, with an 8,000 W (8 kW) load and a required runtime of 1 hour, the batteries used in the UPS should have the following characteristics.
C = (8000W * 1)/(12V * 16 * 0.92 * 0.6) = 75.5AH, where 16 is the number of 12 V batteries in series (192 V DC), and 0.92 is the inverter efficiency.
In other words, a string of 16 batteries rated at 12 V 100 Ah can provide approximately 1 hour of runtime.
Battery aging
Like most electronic devices, batteries are subjected to wear through continuous use, and their runtime decreases over time. One option is to buy batteries with considerably greater capacity from the start (for example, 50% more). Alternatively, it is very important to check battery health regularly or, in light of recent developments, consider a new-generation (lithium) UPS, which offers longer runtime and service life.
Tescom Hellas offers batteries for every type of UPS. Learn more here, along with battery testing and replacement services when needed.
How to increase runtime
- Connect only critical equipment to battery-backed outlets. Never connect laser printers or heating appliances to a UPS.
- Choose a UPS that supports external batteries and has an enhanced charger, such as the XL models in the PRIME PLUS series. Learn more about UPS battery expansion.
- Consider lithium: LiON lithium UPS systems offer longer runtime in the same size.
- Keep batteries cool, around 20–25°C. See how long a UPS lasts.
- For extended outages, a UPS combined with a generator is usually the most economical solution.
Frequently asked questions
How long does a UPS last?
At full load, most small UPS systems run for 3–15 minutes. At a lighter load, they run several times longer. For an accurate estimate, use the formula above or ask us to calculate it.
Why does my UPS run for less time than before?
Battery aging is almost always the cause. Lead-acid batteries in small UPS systems usually last 3–5 years, less in warm environments.
Can I connect a larger battery for more runtime?
Only to a UPS designed for external batteries. The charger in a small UPS is not designed for a much greater battery capacity.
If you need help calculating runtime or have further questions, contact the Tescom Hellas experts, and they will be happy to help.