Generator set installation

How to install a generator set correctly: space and base, ventilation, vibration isolation, soundproofing, exhaust, ATS connection and maintenance.

Short answer: correct generator set installation requires six essentials: a suitable base, adequate ventilation, vibration isolation, soundproofing, proper exhaust discharge and a correct connection to the distribution board, usually through an automatic transfer switch (ATS). We explain each below.

For a correct installation, the following key stages must be taken into account:

First, the area where the genset will be installed must be marked out, as there must be enough space around it for the installation.

The points that then need attention are:

  • Transport and unloading of the genset.
  • Floor (base) supporting the genset.
  • Proper ventilation.
  • Anti-vibration mounts.
  • Sound insulation.
  • Exhaust system.

Transport and unloading of the genset

TESCOM gensets are designed so that transport, loading and unloading can be carried out easily and safely. For this purpose, open-type and soundproof gensets are fitted with a metal base with suitable holes for lifting by crane.

Depending on their size, they can be moved with a forklift, using additional feet that raise the genset off the floor and allow the forks to be inserted.

Floor (base) supporting the genset

Confirming that the floor on which the genset will rest has the load-bearing capacity per m² to support its weight is the most important factor at this stage. This should be a prerequisite and must be checked before the genset is selected and ordered.

If load-bearing capacity is not an issue, the simplest way to secure the generator is with bolts placed through the appropriate holes in the generator's metal frame. You must check that the equipment is firmly secured and that the support areas are level with the ground. Otherwise, equipment vibration may increase and the engine-alternator alignment may be affected. Also, as mentioned at the start, there must be enough space around the genset for technicians to access it comfortably.

Proper ventilation

In indoor installations, both open-type and soundproof gensets require good ventilation for cooling and combustion. To calculate the required ventilation airflow, the following must be added together:

  • Engine combustion airflow.
  • Engine cooling airflow.
  • Alternator cooling airflow.

It is vital to have separate air inlets and outlets to prevent recirculation of the hot air expelled by the engine fan and heating of the generator, as this can cause the genset to shut down due to high temperatures. In practice, this means that the genset room must have a sufficiently large louvered opening. Do not forget the size of the louvers and control of the inlet air temperature: the air temperature must not exceed 40 °C, to prevent derating of the genset.

Do not position the genset so that the radiator is on the same wall as the air inlet, as this would encourage recirculation of hot air in the room, causing overheating.

Anti-vibration mounts

When running, gensets produce vibrations which, if not minimized, can be transmitted to their surroundings, causing noise and damage to the structures that support them. To avoid this, suitable anti-vibration mounts capable of absorbing most of the vibration must be placed under the genset.

All TESCOM gensets include anti-vibration blocks built in between the engine-alternator assembly and the base frame.

For installations where this point is especially critical, there are additional anti-vibration elements, such as springs and elastomeric materials (e.g., Sylomer), that complement and enhance the effect of the anti-vibration blocks.

Sound insulation

The noise generated by a genset is the product of mechanical vibration and the movement of the various parts of the equipment.

Although in many cases we cannot act on the noise produced by the generator itself, it is possible to isolate the machine to reduce it.

Isolation is provided by the walls of the room housing the generator set and by barriers at the cooling air inlets and outlets.

In hospitals or residential areas, genset noise is a major problem that must be solved, and in such cases TESCOM uses and designs accessories to achieve maximum sound insulation. These are:

  • Soundproofed air inlet and outlet baffles (super silent canopy option).
  • Reinforced exhaust silencers (critical silencer option).
  • Double layer of sound-absorbing material in the canopies (super silent canopy option).
  • Acoustic air traps (super silent canopy option).

Exhaust system

To discharge the exhaust gases produced by the engine, and in addition to attenuating the noise produced, there must be an opening in the room to vent the exhaust gases while the genset is running. An exhaust silencer is usually fitted as well.

Proper and complete evacuation of the exhaust gases requires a system of exhaust ducts that vent the gases outdoors (chimneys). TESCOM's technical department will calculate the ideal dimensions of these ducts to ensure the machine operates correctly.

Connection to the distribution board and automatic transfer switch (ATS)

The generator set connects to the electrical installation through a transfer switch so that it can never supply power at the same time as the utility grid. The automatic transfer switch (ATS) detects a grid outage, signals the generator to start and transfers the load once its voltage stabilizes. When utility power returns, it transfers the load back and stops the generator after a cooling period.

The generator's voltage regulator (the alternator AVR) keeps output voltage stable as the load changes. Learn more in our article on automatic voltage regulators (AVRs).

Combining a generator and UPS

Several seconds pass between an outage and the generator taking over. That is enough for computers, servers and automation systems to shut down. Critical loads are therefore supplied by a UPS, which bridges the gap, while the generator covers prolonged outages. The generator must have a sufficient power margin for the UPS it supplies. See how this was applied in an island hotel and a food-packaging line.

Grounding, fuel and safety

  • Grounding: the generator set's frame and neutral are grounded according to electrical installation regulations by a licensed electrician.
  • Fuel: the tank and fuel storage must meet fire safety regulations. Calculate the quantity according to the backup duration you need.
  • Exhaust gases: never operate in an enclosed space without proper discharge outdoors.

Testing and maintenance

  • Test the generator regularly, ideally under load, to confirm that it starts and takes over correctly.
  • Change oil and filters and check the starting battery according to operating hours and the manufacturer's instructions.
  • Check fuel level and quality, because diesel deteriorates when left unused for a long time.

Installation checklist

  • Space around the generator set for technician access
  • Floor with the required load-bearing capacity
  • Separate air inlet and outlet, with louvers
  • Vibration isolation mounts
  • Soundproofing suited to the location
  • Exhaust discharge outdoors
  • ATS and connection to the distribution board
  • Grounding
  • Fuel tank meeting fire safety requirements
  • Load test before handover

Tescom Hellas offers diesel generator sets and provides installation planning.

Frequently asked questions

What is a generator set?

An engine, usually diesel, connected to an alternator that produces electricity. In everyday language, a generator.

What is an ATS?

An automatic transfer switch detects a utility outage, starts the generator and transfers the load to it, reversing the process when utility power returns.

Do I need a UPS if I have a generator?

For computers, servers and automation systems, yes: a generator takes several seconds to take over. A UPS bridges this gap.