Double Conversion Efficiency

The share of input power that an online UPS delivers to its output, lower at light load and highest at medium to high load.

Technical level:Advanced

The efficiency of an online UPS is not constant; it varies with the load percentage. At very low load, the fixed losses of the electronics make up a large share of total consumption and efficiency drops noticeably. As the load rises, efficiency increases, and in modern systems it typically reaches about 94–96% at medium and high loads.

This curve matters in practice when sizing. A UPS that is far too large for its load will run permanently in the low-efficiency range, with higher consumption and more heat.

Practical tip: choose the rating so that the normal load sits at roughly 40–80% of nominal capacity, leaving room for expansion. Ask the manufacturer for the efficiency curve, not just the peak value.