Capacity System

Parallel UPS units that share the load with no spare unit (N configuration), so the failure of one unit overloads the rest.

Technical level:Advanced

In a capacity system, also known as an N configuration, two or more UPS units or modules run in parallel and share the load, with no spare unit. For example, two 10 kVA UPS units together supply an 18 kVA load: the total power is sufficient, but no unit is left over.

This setup is used mainly when more power is needed than a single unit provides. However, if one unit fails, the others become overloaded and the system goes to bypass or shuts down. That is the difference from a redundant N+1 configuration, where one extra unit covers the loss.

If continuity is critical, as in a data centre or hospital, a capacity system is not enough. Size the system so that the load is still covered with one unit missing.