Skip to content
Tescom Hellas S.A.
Articles

Modular UPS: what it is and when it is worthwhile

What a modular UPS is, how it differs from a conventional UPS, and when expansion, N+1 redundancy, and uninterrupted maintenance make it worthwhile.

Short answer: a modular UPS consists of a frame and removable power modules. Add modules as the load grows, achieve N+1 redundancy within the same frame, and replace a module without interruption. It is mainly worthwhile for data centers and critical loads that will grow.

What modular architecture is

UPS systems designed with a modular architecture allow their owners to increase the UPS power rating, improve availability and benefit from scalable solutions. UPS systems of this type offer maximum reliability, since the load is shared across their UPS modules, and they can be maintained and expanded without interrupting operation.

The result is improved performance, a lower cost of ownership and better customer service through high availability.

Modular or conventional UPS

Modular Conventional (monolithic)
Power expansion Add modules to the same frame New or second UPS
N+1 redundancy Within the same frame, with one extra module With a second UPS in parallel
Fault Only the module is removed, using hot swap UPS switches to bypass for repair
Repair time Minutes (module replacement) Usually longer
Initial cost Higher for low power ratings Lower for low power ratings
Suitable for Data centers, growing loads Fixed small and medium loads

Right-sizing: pay for what you need today

With a modular UPS, you buy modules for today's load and add more when needed, instead of buying a large UPS upfront that will operate for years at a low load, where efficiency is lower.

N+1 example

For a critical 40 kW load using 20 kW modules, two modules cover the load (N = 2) and a third provides redundancy (N+1). If one module fails, the other two continue supplying the entire load.

Tescom's TEOS 900 Modular series supports modular architecture. Learn more here.

Frequently asked questions

What is a modular UPS?

A UPS consisting of a frame and removable power modules, allowing you to increase capacity, provide redundancy, and replace modules without interruption.

Is a modular UPS worthwhile for a small server room?

Usually not for a few kVA, where a conventional Online UPS is more economical. It becomes worthwhile when the load is large, will grow, or no interruption is acceptable, even during maintenance.

What does N+1 mean in a modular UPS?

There is one more module than the load needs, so a single module failure does not affect the power supply.


Planning a server room or data center? Contact Tescom Hellas.

Was this helpful?