Operating Temperature and Humidity Range
The limits of room temperature and relative humidity within which a device is designed to operate correctly.
Technical level:Basic
A typical UPS specifies operation from 0 to 40 °C and relative humidity up to 90 or 95% non-condensing. The datasheet usually also gives a separate, wider storage range, which applies only when the device is switched off.
The fact that a UPS operates at 40 °C does not mean its batteries will last. Lead-acid batteries have their best service life at around 20–25 °C, so a storeroom without air conditioning in August wears them out quickly.
The words “non-condensing” matter. If you move a UPS from a cold car or warehouse into a warm room, leave it for a few hours to acclimatise before switching it on, so that moisture on the circuits can evaporate.