Float Charging

A continuous low-level charging method to keep UPS batteries full and prolong their lifespan.

Technical level:Intermediate

Once the battery is full, the UPS charger holds a steady voltage slightly above nominal, enough to make up for self-discharge without overcharging. For a 12 V lead-acid battery this is typically 13.5–13.8 V at 20–25 °C.

The correct float voltage largely determines battery life. Too high a voltage causes drying out and swelling, while too low leaves the battery partly charged and leads to sulphation. That is why many UPS units adjust the voltage according to temperature.

Heat remains the biggest enemy: in a room constantly above 25 °C, the life of a VRLA battery drops considerably, however correct the charging. Place the UPS in a cool, well-ventilated spot.