Altitude Derating

Reduction in the rated power of a UPS, inverter or generator when it is installed above a certain altitude, usually 1,000 metres.

Technical level:Advanced

With altitude the air gets thinner: it cools electronics less effectively and insulates less well between conductors. That is why manufacturers state full power up to a certain altitude, often 1,000 metres, and above it give a derating table or factor. Generators are affected even more, because the engine gets less oxygen.

In Greece this concerns mountain villages, ski resorts and telecom sites on peaks. A 10 kVA UPS at 1,500 metres may not deliver its full rated power; the exact factor is in the manual.

Size the installation using the power after derating, not the nameplate rating, otherwise the UPS may overheat or overload with loads it would normally cover.