UPS topology: how each type works
How Offline, Line Interactive, and Online double-conversion UPS topologies work: diagrams, transfer time, bypass, and IEC 62040-3 classification.
Short answer: there are three main UPS topologies. Offline (Standby) switches to the battery only during a power outage. Line Interactive adds automatic voltage regulation (AVR). Online double conversion continuously powers equipment through its inverter, with no transfer time.
A UPS topology is defined by the basic design of how the UPS operates. The UPS units mainly sold on the market today come in two types of topology: Line Interactive and Online. These two basic topologies work differently and, if the wrong one is chosen, can affect the protected device or the cost of the UPS.
Offline (Standby)
The simplest topology. Under normal conditions, equipment receives power directly from the grid without voltage regulation. If power fails or voltage moves far outside its limits, the UPS switches to the battery with a transfer time of a few milliseconds. This topology is found in very small, inexpensive models.
Single Conversion - Line Interactive
Under normal conditions, these UPS systems take power from the grid (AC) and supply the connected devices directly. If the supply (AC) goes outside the permitted limits, the UPS inverter stops the direct supply and starts supplying power from the batteries until the supply is restored or the batteries are depleted. Tescom offers the well-known LEO series with Line Interactive topology.
Double Conversion - Online
UPS systems with this topology convert power twice. First, an input rectifier converts AC power to DC and feeds the output inverter. Then the output inverter processes and stabilizes the AC supply before sending it to the UPS output.
This double-conversion process completely isolates critical loads from unconditioned power, ensuring that connected equipment receives clean, reliable electricity. In normal operation, a double-conversion UPS continuously converts power twice. If the AC input supply moves outside the permitted limits, the input rectifier stops and the output inverter starts drawing energy from the battery. The UPS continues using battery power until the AC input returns within its limits or the batteries are depleted. Explore Tescom Online UPS systems here .
Static bypass and ECO mode
Online UPS systems have a static bypass: if the inverter is overloaded or develops a fault, the UPS automatically transfers the load directly to the grid to keep equipment running. Many also offer ECO mode, which powers the load through the bypass while grid power is good for higher energy efficiency. The UPS returns to double conversion as soon as a problem occurs.
The three topologies compared
| Offline (Standby) | Line Interactive | Online (double conversion) | |
|---|---|---|---|
| Power supply during normal operation | Directly from the grid | From the grid through AVR | Always through the inverter |
| Voltage regulation | No | Yes, in steps | Continuous |
| Transfer time | A few ms | A few ms | Zero |
| IEC 62040-3 classification | VFD | VI | VFI |
| Typical use | Basic computer | Home, office | Servers, medical equipment, industry |
What VFD, VI, and VFI mean
IEC 62040-3 classifies UPS systems according to how much their output depends on the grid:
- VFD (Voltage and Frequency Dependent): output voltage and frequency follow the grid. This is the Offline UPS category.
- VI (Voltage Independent): output voltage is regulated, while frequency follows the grid. This is the Line Interactive UPS category.
- VFI (Voltage and Frequency Independent): output voltage and frequency are independent of the grid. This is the Online double-conversion UPS category.
Frequently asked questions
What does double conversion mean?
The UPS continuously converts grid AC power to DC and back to AC. Equipment therefore always receives clean power from the inverter and experiences no interruption.
What is VFI?
The IEC 62040-3 category for UPS systems whose output is independent of grid voltage and frequency: Online double-conversion UPS systems.
What is ECO mode?
An energy-saving mode in Online UPS systems: while grid power is good, the load is supplied through the bypass. The UPS returns to double conversion as soon as a problem occurs.
Learn more about how to choose the UPS topology that will support you properly and cost-effectively here.