Single-phase or three-phase UPS: which should I choose?
Choose a single-phase or three-phase UPS for your utility supply and load: 1/1, 3/1 and 3/3 systems from 1 kVA to 600 kVA.
Short answer: your UPS should match your supply and loads. For devices connected to outlets (computers, servers and networking equipment), a single-phase UPS is usually sufficient, even if the building has a three-phase supply. A three-phase UPS is needed when critical loads are large (above roughly 10 kVA) or three-phase, such as motors and industrial machinery.
The two types of electrical supply
There are two options for the electrical supply:
Single-phase, with a voltage of 230 V, 1x35A and a maximum power of 8,000 W. Three-phase, with a voltage of 400 V, 3x35A and a maximum power of 24,000 W.
UPS categories by electrical supply
Depending on the supply available at the electrical panel and the application that needs protection, the corresponding UPS can be used:
• Single-phase input / output, Plug n’ Play, with an apparent power of 1-3 kVA. In UPS systems of this category, devices can be plugged directly into the UPS's output outlets.
• Single-phase input / output with a terminal block, with an apparent power of 6-10kVA.
Tescom offers 2 single-phase input/output series: NEOLINE, PRIME PLUS
• Three-phase input / single-phase output, with an apparent power of 6-10kVA.
TEOS 400 RT/R systems support three-phase input and single-phase output.
• Three-phase input / output, with an apparent power of 30-600kVA. Explore three-phase UPS systems here.
Single-phase UPS systems with a terminal block and all three-phase UPS systems may only be connected to the device or network they protect by a qualified technician, through an electrical panel.
What 1/1, 3/1 and 3/3 mean
The first number indicates the phases at the UPS input, and the second indicates the phases at its output.
| Type | Input / output | Typical power | Tescom series |
|---|---|---|---|
| 1/1 | Single-phase / single-phase | 1–10 kVA | NEOLINE, PRIME PLUS, LiON |
| 3/1 | Three-phase / single-phase | 10–20 kVA | TEOS 400 RT/R (RT FLEX) |
| 3/3 | Three-phase / three-phase | 10–600 kVA | TEOS 400, DS 300, DX |
A 3/1 UPS draws power from all three phases, so it does not load just one phase of the distribution board, while supplying single-phase loads.
I have a three-phase supply: do I need a three-phase UPS?
Not necessarily. Most critical loads in an office or store are single-phase. If the total critical load is a few kW, a single-phase UPS connected to one phase is the simplest solution. Work with your electrician to make sure that phase is not overloaded relative to the others.
You need a three-phase UPS (3/3) when:
- there are three-phase loads, such as motors, pumps and production machinery,
- the critical load is large and needs to be distributed across three phases,
- you want one central UPS for the whole building, as in the hotel with a 30 kW UPS or the packaging line with a 60 kVA UPS.
For UPS sizing, see our guide to UPS power.
Frequently asked questions
Can I connect a single-phase UPS to a three-phase supply?
Yes. A single-phase UPS connects to one phase and supplies single-phase loads. For larger loads, a 3/1 UPS distributes consumption across three phases.
What does a 3/1 UPS mean?
Three-phase input and single-phase output. It draws power from three phases and supplies single-phase equipment.
From what kVA rating is a three-phase UPS needed?
Usually from around 10 kVA upward, or when there are three-phase loads.