What rack size do you need? U, depth and weight
Choose the right rack size: height in U with an example, depth, 600/800 mm widths, weight limits and room for future equipment.
Short answer: add up the U height of your equipment, allow around 30% free space for future additions and ventilation, and choose a depth that comfortably accommodates your deepest device. A 12U wall-mounted cabinet is usually sufficient for a small office; for servers and UPS systems, you need a floor-standing cabinet, 800–1000 mm deep.
Height
Rack height is measured in U. Each U is 1.75 inches or 44.45 mm. For example, a 42U cabinet has an internal height of 42 × 1.75 = 73.5 inches / 1866.9 mm. A rack server usually occupies 1U–2U. A 1–3 kVA rack UPS usually occupies 2U, and each external battery pack another 2U. Calculate accurately the height of the equipment to be housed, as well as the space available for equipment that may be added later.
Example: 1U switch + 2U patch panel + 2U UPS + 2U camera recorder + 2U shelf = 9U. With a 30% margin (≈ 12U), a 12U wall-mounted cabinet is the right choice.
Depth
Choose the cabinet's depth according to the equipment it will house.
Floor-Standing Rack
Some indicative equipment depths.
| Rack | Depth (mm) | Ideal for |
|---|---|---|
| Shallow | 690 | A/V equipment, limited space |
| Medium depth | 790 | Limited space |
| Standard | 940 | Servers |
| Deep | 1070 | Extra cables, better airflow |
Wall-Mount Rack
Some indicative equipment depths.
| Rack | Depth (mm) | Ideal for |
|---|---|---|
| Shallow | < 410 | Patch panels |
| Medium depth | 410 - 610 | Switches |
| Standard | 611 - 810 | UPS systems |
| Deep | > 810 | Servers |
Typical European sizes
| Type | Height | Width × depth (mm) | Maximum weight | Lande series |
|---|---|---|---|---|
| Wall-mounted | 6–18U | 600 × 450, 600 × 600 | 80 kg | WB PROlineB |
| Wall-mounted | 6–20U | 600 × 450, 600 × 600 | 100 kg | PROlineB |
| Floor-standing (flat-packed) | 22–42U | 600 or 800 × 600 to 1000 | 600 kg | DYNAMIC BASIC |
| Floor-standing for servers | 12–45U | 600 or 800 × 1000 | 1000 kg | DYNAMAX |
| Floor-standing networking | 16–47U | 600 × 600 to 1000 | HYPERLINE |
Width: 600 or 800 mm
All cabinets accommodate 19″ equipment. An 800 mm width leaves room at the sides for vertical cable management and is preferable when there are many patch panels or switches with dense cabling.
Equipment weight
Rack cabinets can accommodate equipment up to a specified weight limit. Make sure the total weight of the equipment does not exceed the cabinet's permitted load.
Learn more about special rack features here.
Frequently asked questions
How many U do I need?
As many as your equipment needs today, plus around 30%. Empty U spaces are covered with blanking panels for correct airflow.
What rack depth do servers need?
Usually 1000 mm, because rack servers and rack UPS systems are deep and also need cable space at the rear.
A width of 600 or 800 mm?
600 mm for simple installations. 800 mm when there is dense cabling and vertical cable management is needed at the sides.
Need help choosing a cabinet? Contact Tescom Hellas.